Hard-Water Solar Hot Water Systems: Scale Prevention, Heat Exchanger Design and Cleaning Access
Hard-Water Solar Hot Water Systems: Scale Prevention, Heat Exchanger Design and Cleaning Access
A solar hot water system for a hard-water site needs a defined water-treatment strategy and a heat-transfer path that can be inspected and cleaned. An indirect collector circuit can protect the roof equipment from the incoming domestic water, but the potable-water side of the exchanger, tank and downstream heater still needs attention.

The purchasing decision therefore extends beyond the collector material. Identify where untreated water flows, which surfaces become hot, and how those surfaces will be serviced without an unacceptable hot-water outage. A modestly priced exchanger that can be isolated and cleaned may be a better project choice than a more expensive assembly whose service surfaces are inaccessible.
This guide follows that decision from the water report through exchanger selection and performance checks. For the separate question of copper versus aluminium absorber construction, see the Cu-Cu and Cu-Al selection guide.
Locate the water exposure before specifying a solution
Hardness is associated mainly with dissolved calcium and magnesium. Mineral deposits can obstruct flow and impair heat transfer, particularly at heated surfaces, as illustrated by the USGS explanation of hard-water deposits. The actual deposit and its growth depend on the water chemistry and operating conditions.
Draw the system as separate fluid circuits. Mark the source of every fill and top-up connection, including any connection normally closed during operation.
| System arrangement | Where source water is exposed to heat | Design implication |
|---|---|---|
| Direct circulation through the collectors | Collector passages, connecting pipework and hot-water storage | Water suitability and cleaning access must include the roof circuit |
| Closed solar loop with an internal tank coil | Source water contacts the outside of the coil and the potable tank surfaces | Check tank inspection access and whether the coil's water-side surface is practically cleanable |
| Closed solar loop with an external exchanger | Source water passes through the exchanger's domestic-water channels, then storage or the load | Provide isolation, instrument connections and an approved cleaning route on that side |
| Non-potable thermal store with a separate domestic-water exchanger | Domestic water remains in the separate exchanger and distribution circuit | Reduced stored potable volume does not eliminate scale exposure in the exchanger |
The U.S. Department of Energy's solar water-heating assessment distinguishes the collector-loop protection of indirect arrangements from continued scaling exposure on the potable-water side. Closed-loop design also needs a suitable fill fluid; routinely adding untreated mains water after leaks can undermine the intended separation and fluid condition.
Changing the absorber fin from aluminium to copper does not change the hardness passing through an otherwise identical copper waterway. Trace the wetted surfaces first, then specify their materials and the water they will receive.

Ask for a water report that supports an equipment decision
“Hard water” is not a complete specification. Obtain a sample representative of the water entering the plant, record the sampling point and date, and identify any existing treatment. If boreholes or municipal sources are switched seasonally, the designer needs the relevant range rather than one favourable sample.
The equipment and water-treatment suppliers should review at least the following information, with additional parameters where the source or application warrants them:
| Input | Question it helps answer |
|---|---|
| Total hardness, reported with units such as mg/L as CaCO₃ | What hardness load reaches the hot-water plant? |
| Calcium, alkalinity, pH and operating temperatures | What further assessment of carbonate scaling is needed? |
| Chloride, conductivity or dissolved-solids data | Are the proposed wetted materials suitable for the actual water? |
| Suspended solids, iron or manganese where relevant | Is particulate fouling or another deposit likely to complicate the problem? |
| Disinfectant type and concentration | Is the water compatible with the proposed metals, elastomers and treatment equipment? |
| Peak flow, daily volume and supply pressure | Can treatment serve the real duty without excessive pressure loss or untreated bypass? |
| Existing treatment and its operating records | Does the sample represent raw water or water after treatment, and is treatment reliable? |
Ask the exchanger manufacturer to state the acceptable water-quality envelope for the proposed plates, braze or weld material, seals and duty. A generic label such as “stainless steel” does not define all of those components.
Avoid adopting one universal hardness cutoff for direct circulation or one chloride limit for every stainless-steel exchanger. The defensible choice is a documented match between the water report, operating conditions and the selected equipment's requirements.
Put hardness values on one reporting basis
Water reports and treatment quotations may use different units. The following conversions put them on a common calcium-carbonate-equivalent basis; mmol/L here means the sum of the molar concentrations of calcium and magnesium ions.
| Reported unit | Equivalent hardness, mg/L as CaCO₃ |
|---|---|
| 1 mmol/L of Ca²⁺ plus Mg²⁺ | 100.09 |
| 1 °dH, German degree | 17.85 |
| 1 °fH, French degree | 10.0 |
| 1 grain per US gallon, gpg | 17.1 |
Do not substitute total hardness for calcium hardness in a calculation that specifically requires calcium. Likewise, a laboratory result in mg/L of calcium ions is not already mg/L as CaCO₃.
The USGS classification calls 0–60 mg/L soft, 61–120 moderately hard, 121–180 hard and values above 180 very hard. The UK Drinking Water Inspectorate publishes different bands: up to 100 soft, 100–150 slightly hard, 150–200 moderately hard, 200–300 hard, and above 300 very hard, all as CaCO₃. Thus the 250 mg/L example below is “very hard” under USGS and “hard” under DWI. Specify the measured number and unit; a category name is neither a treatment target nor an equipment limit.
Why identical hardness does not mean identical scaling behaviour
Hardness describes a concentration; carbonate deposition is an equilibrium and rate problem. Calcium availability, alkalinity, pH, temperature and dissolved constituents affect the assessment. A USGS investigation explaining the Langelier Saturation Index identifies calcium hardness, alkalinity, dissolved solids and temperature among its inputs. A positive index indicates calcium-carbonate supersaturation under the evaluated conditions.
That index does not state how many kilograms will adhere to a particular plate exchanger or how soon it will need cleaning. Flow, hot-surface conditions, residence time and the nature of existing deposits still matter. Nor does one calcium-carbonate index certify compatibility with every metal, braze or elastomer.
Ask the water specialist to evaluate the actual heated-water duty, not just return a number calculated at the cold sampling temperature. The heat-transfer surface can be hotter than the measured bulk water. A cold-water report therefore needs to be interpreted alongside source-fluid temperatures and the exchanger duty. Record how pH and chemistry are treated as the water heats; simply changing a temperature entry while assuming every other equilibrium variable stays fixed can create false precision.
This produces two separate purchasing decisions: how to limit deposition, and whether the water is compatible with all wetted components. Successful hardness removal does not by itself close the second question.
Calculate temperature sensitivity without inventing a deposition rate
The simplified LSI formulation reproduced in the USGS investigation uses the following relationships. All logarithms are base ten; TDS is in mg/L, calcium hardness and total alkalinity are in mg/L as CaCO₃, and T is in °C.
pHs = (9.3 + A + B) − (C + D) LSI = pH − pHs A = (log10(TDS) − 1) / 10 B = −13.12 × log10(T + 273) + 34.55 C = log10(calcium hardness) − 0.4 D = log10(total alkalinity)
Use hypothetical TDS of 400 mg/L, calcium hardness of 200 mg/L as CaCO₃, alkalinity of 180 mg/L as CaCO₃ and pH 7.6. Hold all these inputs fixed solely to isolate the formula's temperature sensitivity. Then A = 0.160206, C = 1.901030 and D = 2.255273:
| Evaluated temperature | B | Calculated pHs | Calculated LSI |
|---|---|---|---|
| 15°C | 2.282771 | 7.586674 | +0.013326, approximately zero |
| 60°C | 1.455532 | 6.759435 | +0.840565 |
The formula predicts greater supersaturation at the higher temperature under those fixed-chemistry assumptions. It does not establish the actual hot-wall LSI: pH, gas exchange and precipitation can change the chemistry during heating. The extra digits make the arithmetic reproducible, not the water analysis that precise. Nor does +0.84 specify a scale mass or cleaning interval.
Hach method 8073 provides an alternative tabulated-factor method. Its factors have different definitions; do not combine Hach's tables with the A–D equations above or attribute this algebraic form to that method.
The relevant local surface can be hotter than bulk domestic water. For a separate idealised wall estimate, equal film coefficients and negligible wall resistance put the wall approximately halfway between local fluid temperatures: 70°C and 45°C give 57.5°C. Actual coefficients, wall resistance and temperature profiles determine the real value. Ask for the hottest expected potable-side surface condition during charging, then coordinate any charging-temperature limit with hygiene, scald protection and the solar circuit's response when the store cannot accept more heat.
A hardness-load calculation has a limited but useful role
Assume, for illustration, that a commercial plant uses 5,000 L/day of water with hardness of 250 mg/L as CaCO₃. The incoming hardness equivalent is:
5,000 L/day × 250 mg/L ÷ 1,000,000 mg/kg = 1.25 kg/day as CaCO₃ equivalent
This is the amount passing into the plant on that reporting basis. It is not a prediction of 1.25 kg of scale depositing each day. The calculation is useful when discussing treatment capacity and the consequence of an untreated bypass; precipitation and the location of deposits require a separate assessment.
Match treatment to the problem it can actually address
A strainer protects equipment from particles already present in the water. It does not provide the same function as removing dissolved hardness. Request the treatment mechanism and verified capability rather than accepting “filter included” as a complete scale-control strategy.
EPA describes cation-exchange softeners as replacing calcium and magnesium with sodium or potassium. It also identifies the water and salt consumed during regeneration. For a commercial solar hot-water project, this creates practical questions about peak flow, usable capacity, regeneration timing and how service continues during regeneration.
| Proposed measure | Useful role | Requirement to resolve before purchase |
|---|---|---|
| Strainer or sediment filter | Limits particulate entry and protects passages | Mesh or filtration rating, clean and service pressure loss, access and cleaning responsibility |
| Cation-exchange softener | Reduces calcium and magnesium hardness | Treated-water target, capacity at actual demand, regeneration, bypass status and operating cost |
| Reverse osmosis where justified | Addresses specified dissolved constituents | Verified rejection, recovery, concentrate disposal and suitability of the resulting water |
| Chemical or other scale-control treatment | May address a defined deposit mechanism | Potable-water suitability, evidence at the actual duty, dosing or operating control, and equipment compatibility |
| Scheduled exchanger cleaning | Restores a serviceable heat-transfer surface when deposits form | Proven cleaning method, access, outage plan and confirmation of restored performance |
The CDC water-treatment overview explains why treatment selection must follow the substance being removed. Softening is not disinfection, and a treatment chosen for hardness should not be assumed to solve every corrosion or water-quality issue.
For high-continuity loads, address treatment downtime explicitly. A bypass that keeps water flowing may also send untreated water to the exchanger. A duty/standby or alternating arrangement may be justified, but it should follow the project's continuity requirement rather than being added automatically.
Size treatment by both exchange capacity and peak service flow
Continue the hypothetical 5,000 L/day case. Suppose the agreed residual-hardness target is 25 mg/L as CaCO₃, and a supplier quotes 5.0 kg of working exchange capacity per regeneration at the proposed salt setting and water conditions. Assume the project reserves 20% of that capacity before switching or regenerating. These are example inputs, not a recommended hardness target or a resin performance claim.
Hardness removed = 250 − 25 = 225 mg/L as CaCO₃ Daily removal load = 5,000 × 225 / 1,000,000 = 1.125 kg/day Usable capacity before the assumed reserve = 5.0 × 0.80 = 4.0 kg Treated volume before that point = 4.0 × 1,000,000 / 225 ≈ 17,778 L Average time to that point = 4.0 / 1.125 ≈ 3.56 days
The calculation supports a volume-based service discussion. It does not mean that regeneration every fourth calendar day is adequate regardless of demand. Higher occupancy or a raw-water hardness increase shortens the run.
At 5,000 L/day, the 24-hour average is only about 3.47 L/min. If the plant's measured peak feed is 30 L/min, however, the treatment equipment must meet its outlet-quality and pressure-loss requirements at 30 L/min. Selecting it on the daily average could leave adequate nominal capacity but inadequate treatment during shower peaks.
The quotation should therefore state working capacity at the proposed regeneration setting, permitted service flow, pressure loss and regeneration consumption. At commissioning, check treated-water hardness during peak operation and near the intended regeneration point. Record bypass position and supply interruptions. Otherwise, an apparently functioning softener can coexist with repeated untreated-water exposure.
Include sodium in a sodium-cycle softening calculation
In a sodium-cycle exchanger, replacing one mmol of divalent calcium or magnesium introduces two mmol of sodium. The stoichiometric mass ratio is approximately 2 × 22.99 / 100.09 = 0.4594, or about 0.46 mg of added sodium per mg of hardness removed as CaCO₃. This sodium calculation does not describe a potassium-cycle softener.
Using the rounded factor in the example, removing 225 mg/L of hardness adds about 225 × 0.46 = 103.5 mg/L sodium. Add the raw-water sodium concentration: an assumed starting value of 100 mg/L would give about 203.5 mg/L after treatment.
Directive (EU) 2020/2184, Annex I Part C lists 200 mg/L as the sodium indicator parametric value. The DWI's softener guidance also advises retaining an unsoftened kitchen supply for drinking and cooking. Evaluate the site's treatment and potable-water requirements with its actual sodium result and applicable local rules. A hardness target alone does not complete the water-quality specification.
Select the exchanger together with its service method
Size the exchanger against the intended temperatures, flows, fluids and pressure-loss limits. Then assess how performance will change between cleanings and how the unit can be restored. The solar thermal heat-exchanger sizing guide explains the thermal-duty calculation; the additional decision here is maintainability.
| Exchanger option | Service advantage | Limitation to resolve |
|---|---|---|
| Gasketed plate exchanger | Plates can generally be opened for inspection and mechanical cleaning according to the manufacturer's procedure | Opening clearance, lifting access, gasket suitability and correct reassembly are necessary |
| Brazed or welded compact exchanger | Compact package; approved cleaning-in-place may be possible | Many assemblies cannot be opened in the field, so cleaning effectiveness and replacement access matter |
| Internal tank coil | Fewer external components and connections | The scale-exposed outer surface may be difficult to reach or replace |
| External domestic-water exchanger with a thermal store | Allows the serviceable exchanger to sit in an accessible plant-room position | Additional pumps and controls require coordination; scale remains a domestic-side issue |
Alfa Laval's plate-exchanger maintenance manual describes both cleaning-in-place and manual cleaning. It also notes that severe or insoluble fouling may require opening the exchanger. That is a reason to decide the service route before installation, not a guarantee that every compact unit can be recovered chemically.
A useful installation drawing should show how the relevant circuit can be isolated, cooled, depressurised and drained; where a cleaning unit connects; how cleaning liquid is contained; and how the system is rinsed and returned to service. Identify pressure protection for any trapped heated volume. Put instrument taps where exchanger pressure loss can be distinguished from a blocked upstream filter.
Check the physical removal route as well. Service ports behind a fixed tank or an exchanger that cannot pass through the plant-room door do not constitute usable maintenance access.
Establish a clean baseline before diagnosing scale
At commissioning, retain the four exchanger temperatures, both circuit flow rates, relevant pressure readings, valve positions, fluid identity and delivered heat. Record them at a stable, identified operating condition after the circuit is properly filled and vented.
A later drop in delivery temperature is not enough to diagnose fouling. First compare the hot and cold inlet conditions and flows. A colder solar supply, warmer receiving tank, stuck bypass or incorrect sensor can change the result without any deposit forming.
The following hypothetical water-to-water example demonstrates a comparable test. Both sides carry 0.30 kg/s; specific heat is assumed constant at 4.18 kJ/(kg·K). Both inlet temperatures and flows remain unchanged between observations.
| Reading | Clean baseline | Later observation |
|---|---|---|
| Hot side inlet / outlet | 70°C / 40°C | 70°C / 48°C |
| Cold side inlet / outlet | 15°C / 45°C | 15°C / 37°C |
| Heat transferred on either side | 37.62 kW | 27.59 kW, rounded |
Baseline: 0.30 × 4.18 × (45 − 15) = 37.62 kW Later: 0.30 × 4.18 × (37 − 15) = 27.588 kW
Calculate apparent thermal conductance, not just lost outlet temperature
The two-sided heat balance is the first check. Here the hot-side heat removal exactly equals the cold-side heat gain in each observation. In the field, significant disagreement beyond the measurement uncertainty is a reason to investigate sensors, flows, heat loss and transient operation before calculating a fouling trend.
For a simple counterflow exchanger, define the two terminal temperature differences as:
ΔT1 = hot inlet − cold outlet ΔT2 = hot outlet − cold inlet LMTD = (ΔT1 − ΔT2) / ln(ΔT1 / ΔT2) Q = UA × LMTD
UA is overall thermal conductance: heat-transfer coefficient multiplied by area. Alfa Laval's heat-transfer calculation method sets out the heat-balance and logarithmic-mean-temperature-difference relationships. Use the applicable correction or rating method for other flow arrangements. Do not confuse a difference between the two outlet temperatures with either of these terminal approaches.
When the two terminal differences are equal, LMTD equals that common difference; evaluate this limiting case rather than dividing zero by zero. In the example:
| Derived quantity | Clean baseline | Later observation |
|---|---|---|
| Hot inlet minus cold outlet | 25 K | 33 K |
| Hot outlet minus cold inlet | 25 K | 33 K |
| LMTD | 25 K | 33 K |
| Apparent UA | 37.62 / 25 = 1.5048 kW/K | 27.588 / 33 = 0.8360 kW/K |
Heat duty has fallen by 26.7%, but apparent UA has fallen by 44.4%. They are different quantities because the reduced transfer leaves a larger temperature driving force across the exchanger. The additional apparent resistance of the whole unit is:
1 / UA_later − 1 / UA_clean = 1 / 0.8360 − 1 / 1.5048 ≈ 0.532 K/kW
This is a whole-exchanger resistance change, not an area-based fouling factor in m²·K/W. Inferring such a factor requires the effective area and a suitable clean-versus-fouled model. Temperature-dependent fluid properties and film coefficients can also change apparent UA. A precise diagnosis therefore compares the observation with the manufacturer's clean rating at the actual conditions.
Use effectiveness–NTU to check the same heat balance
For the example's equal heat-capacity rates in ideal counterflow, C = 0.30 × 4.18 = 1.254 kW/K, NTU = UA / C and effectiveness ε = NTU / (1 + NTU):
| Condition | NTU | Effectiveness | Duty, ε × C × (70 − 15) |
|---|---|---|---|
| Clean | 1.20 | 0.54545 | 37.62 kW |
| Later | 0.66667 | 0.40000 | 27.588 kW |
This independently expresses the same thermal model. At unchanged flows and approximately unchanged properties, it can estimate duty for different inlet temperatures. Changing flow requires rerating UA as well because film coefficients change. Unequal heat-capacity rates also require the appropriate counterflow effectiveness relation using C_min/C_max; the simple equation above then ceases to apply. A single measured UA is not a universal rating across all operating conditions.
Quantify how a thin deposit affects different clean U values
Continue with an illustrative model, not a measured deposit. Assume the clean U is 4,000 W/(m²·K). The implied effective area is 1,504.8 / 4,000 = 0.3762 m². Multiplying that area by the whole-unit resistance increase, after converting K/kW to K/W, gives:
R_f = 0.3762 × (1 / 0.8360 − 1 / 1.5048) / 1,000 = 0.0002 m²·K/W
If a uniform deposit had an assumed conductivity of 1 W/(m·K), thickness = R_f × conductivity = 0.0002 m, or 0.2 mm. Deposit conductivity, distribution and effective exchanger area must be established before treating this as a physical thickness estimate.
Holding the clean film resistances unchanged and adding that same R_f gives U_fouled = 1 / (1 / U_clean + R_f):
| Assumed clean U, W/(m²·K) | Calculated fouled U, W/(m²·K) | Reduction in U |
|---|---|---|
| 5,000 | 2,500 | 50.0% |
| 1,500 | 1,154 | 23.1% |
| 500 | 455 | 9.1% |
These are sensitivity cases, not guaranteed ratings for plate exchangers or tank coils. The higher the clean U, the larger the proportional effect of an added resistance. The table does not show the same percentage reduction in heat duty, which also depends on temperatures, flow and area. Ask suppliers to rate both clean and anticipated fouled conditions while stating the assumed deposit resistance, available area, pressure loss and cleaning method. That comparison supports exchanger selection more reliably than choosing a construction type from a generic U value.
Use pressure measurements to narrow the cause
Suppose, as a further hypothetical observation at the same flow, domestic-side exchanger pressure loss has risen from 25 to 42 kPa, while the separate upstream strainer has changed only from 6 to 7 kPa. That localises much of the additional restriction to the exchanger. The combination of reduced conductance and increased local pressure loss supports an internal-fouling investigation, although it still does not identify the deposit's chemistry.
A different pattern calls for a different action:
| Evidence after checking comparable inlet conditions | Most useful next investigation |
|---|---|
| Domestic flow has fallen and pressure loss is concentrated across the strainer | Inspect the strainer, restore flow and repeat the thermal test before condemning the exchanger |
| Flows are stable, heat balances close, UA falls and exchanger pressure loss rises | Investigate internal restriction or fouling; review water and deposit evidence |
| Heat duty falls, but inlet temperatures or flows also change materially | Rerate the clean exchanger at the new conditions before calculating degradation |
| One temperature moves erratically or the two heat balances disagree substantially | Check the sensor installation, data timing, entrained air and bypass paths |
| Thermal performance deteriorates with little pressure-loss change | Investigate an insulating deposit, maldistribution or another thermal limitation; absence of a large pressure rise does not clear the exchanger |
Compare pressure loss at matched flow and fluid condition. A variable-speed pump can maintain flow by increasing head, concealing obstruction if only total flow is observed. Conversely, a changed flow alone changes pressure loss; a fixed percentage pressure-rise alarm without a flow basis can mislead. Manufacturer curves are preferable to an assumed universal pressure-versus-flow exponent.
One idealised sensitivity check illustrates how narrowing a passage can matter. A 2.5 mm gap with an assumed 0.2 mm deposit on each wall becomes 2.1 mm, or 84% of its original width. Fully developed laminar flow between wide, smooth parallel plates at fixed volume flow and viscosity has pressure loss proportional to the inverse cube of the gap. That model gives 1 / 0.84³ = 1.687, turning 25 kPa into about 42.2 kPa.
The numerical resemblance to the hypothetical observation is not independent confirmation of a 0.2 mm deposit. The gap, deposit conductivity and clean U were assumed; a corrugated plate exchanger can have different flow behaviour, port losses and nonuniform deposits. Use this calculation to understand sensitivity, then use the actual exchanger curve, inspection or deposit evidence to investigate the cause.
If delivery was poor from the first day, also revisit the original duty and selection. Cleaning cannot correct an exchanger selected for the wrong inlet temperatures or an unavailable source flow.
Make cleaning a controlled recovery process
Set inspection and service triggers from the water condition, manufacturer instructions and observed performance trend. A site with reliable treatment and a stable baseline may need a different interval from one with frequent untreated bypass or changing source water.
For a suspected deposit, use the following recovery sequence:
Confirm the deterioration under comparable conditions and preserve the readings.
Identify the likely deposit and review the exact exchanger, seals and approved cleaning method.
Plan the hot-water continuity arrangement and isolate the work safely under the equipment procedure.
Use the manufacturer's specified cleaning process. Chemical concentration, temperature and exposure time must be compatible with the actual assembly.
Complete the required rinsing, disposal, integrity checks and potable-water return-to-service procedure.
Repeat the baseline test and record whether heat transfer and pressure loss have recovered.
If performance does not recover, do not assume that stronger chemicals are the answer. Confirm the flow and sensors, investigate insoluble deposits or damage, and consider inspection, reconditioning or replacement where the construction allows it.
A hypothetical post-cleaning retest at the original 70°C and 15°C inlets and 0.30 kg/s on both sides gives a hot outlet of 41°C and cold outlet of 44°C. Heat transfer is 0.30 × 4.18 × 29 = 36.366 kW; both terminal differences are 26 K, giving UA = 36.366 / 26 ≈ 1.399 kW/K. That is 96.7% of the original heat duty and about 92.9% of its apparent conductance. The report can now state what recovered and what remains different. Acceptance depends on the agreed service criterion and measurement uncertainty, not an invented universal recovery percentage.
For a unit that cannot be opened, request evidence that the approved cleaning process can reach the affected channels. A return of cleaning liquid through an external bypass does not prove those channels were cleaned. Include replacement access in the original design when an unsuccessful cleaning attempt would otherwise leave the building without a workable recovery route.
Put the energy penalty and service cost on the same basis
Use the verified loss only during periods when useful source heat and demand would both have been available. Multiplying a peak exchanger shortfall by every hour of the year exaggerates its cost.
In the same hypothetical case, the difference between clean and degraded duty is 37.62 − 27.588 = 10.032 kW. If that difference persisted for four useful operating hours per day over 80 days, lost useful heat would be:
10.032 × 4 × 80 = 3,210.24 kWh of heat
If backup supplied all of that heat at an assumed COP of 2.8, the added electricity would be about 1,147 kWh. At an assumed electricity price of $0.20/kWh, that is approximately $229. These invented operating and price inputs illustrate the method; they are not a forecast or a service quotation.
Compare this energy cost with treatment consumables, cleaning labour, lost service, replacement parts and the consequence of allowing the condition to worsen. With a boiler, use its applicable fuel-to-useful-heat efficiency instead of a heat-pump COP. If the solar field could not have supplied the lost duty, model the coupled system rather than crediting the entire exchanger difference as lost solar production.
Maintain the building's water-hygiene and delivery-temperature requirements throughout the design. Reducing storage temperature simply to reduce scale can create a different problem; hygiene and scald protection belong to the site's approved water-management strategy. The solar hot-water hygiene guide explains that separate design responsibility.

What a useful quotation should contain
Request a water-quality acceptance statement, the exchanger duty sheet, treatment assumptions, cleaning provisions and a defined clean-performance record. Ask who supplies replacement seals or a replacement exchanger, how long service will interrupt hot water, and what condition triggers intervention.
For a SOLETKS enquiry, send the source-water report, daily and peak draw, required temperatures, existing plant arrangement and available service space through the project contact page. Those inputs allow the solar package to be discussed alongside the water-treatment and maintenance requirements that determine its long-term usefulness.